Hello blurt friends. how are you all? I hope all of you are always in good condition, healthy, abundant, and full of love. Amen.
Today I have started work again. In the morning I went to the office.
Earlier when we were measuring the amperage load for the monthly report data, we received a complaint report from the user, that the AC in the room was not cold. We immediately went to the location and repaired the damage that occurred to the AC that was not cold.
The first step is to check the freon pressure and amperage measurements in the outdoor AC unit. From the results of these measurements, we can find out the analysis of the damage that occurred.
From the measurement results, the freon pressure is 75 psi and the ampere measurement is 5.30 amperes. From the results of these measurements, it is known that the AC unit lacks freon. Because the standard 2Pk AC unit is 7 amperes and the standard freon pressure for the R32 liquid type is 150 psi.
We started looking for the cause of the liquid freon can be reduced. There must be a leak in the outdoor AC pipe line to the indoor AC. We use soapy water to find the point of the leak. After we found the point of the leak and we solved the cause of the leak, then we refilled the liquid freon.
After enough liquid freon according to the standard type of AC unit, we checked the AC unit in the indoor. The indoor air conditioner is already very cold and the room is getting cold too. We finished our work and tidy up all the equipment we used. Ensure that the outdoor air conditioner is operating normally.
That's all I can share on my blog for today. Thank you for visiting my blog. See you tomorrow.
** Your post has been upvoted (1.95 %) **
Curation Trail Registration is Open!
Curation Trail Here
Delegate more BP for better Upvote + Daily BLURT 😉
Delegate BP Here
Thank you 🙂 @tomoyan
https://blurtblock.herokuapp.com/blurt/upvote